Transormer oils Т-1500 and ТК All-Union State Standard 982-80 Transformer oils T-1500 and TK — sulfuric and solvent refined oils are produced from low-sulfur crude oils. The oils are used as oil circuit breakers and other high-voltage equipment as the primary insulating material. Transformer oil is solvent refined All-Union State Standard 10121-76 Transformer solvent refined oil TSO is designed to fill the oil-filled transformers and other electrical equipment.
| Index name |
Т-1500 |
ТК |
ТСО |
Kinematic viscosity at, mm² / с, not more than: at 50 °С at 20 °С at minus 30 °С, |
8 – 1100 |
8 30 – |
9 28 1300 |
| Acid number, mg КОН / g, not more than |
0,01 |
0,05 |
0,02 |
Temperature, °С: flash point in an open crucible, not lower than pour point, not higher than |
135 – 45 |
135 – 45 |
150 —45 |
Fraction of total mass, %, not more than: mechanical impurities water soluble acids and alkalis phenol sulphur |
None None – – |
None None None 0,6 |
| The loss tangent of a dielectric, %, not more than |
0,5 (At 90 °С) |
2,5 (at 70 °С) |
1,7 (at 90 °С) |
Stability against oxidation: sediment mass fraction in oxidized oil, %, not more than acid number after oxidation, mg КОН / g, not more than |
Oxidation 0,2 |
0,1 0,35 |
0,015 0,3 |
|